Volumetric Flow Rates: CFM, ICFM, ACFM, SCFM.  What Does it All Mean?

Flow rate is the quantity of material that moves over a period of time.  Generally, the quantity of material can be expressed as a mass or a volume.  For example, mass flow rates are generally in units of pounds per minute (lbs./min) or kilograms per hour (Kg/hr).  Volumetric flow rates are stated in cubic feet per minute (CFM) or liters per hour (LPH).  The trick begins when volumetric flow rates are used for a compressible gas.  In this blog, I will cover the various acronyms and the reasons behind them.

What acronyms will be covered?

CFM – Cubic Feet per Minute

SCFM – Standard Cubic Feet per Minute

ACFM – Actual Cubic Feet per Minute

ICFM – Inlet Cubic Feet per Minute

The volumetric component of the flow rate above is CFM or Cubic Feet per Minute.  This term is commonly used in rating air compressors and pneumatic equipment.  From their history, they would calculate the volume of air being drawn into the air compressor by the size of cylinder.  With the rotations per minute of the motor, RPM, they could calculate the volumetric flow rate.  As conditions change, like altitude, temperature, and relative humidity, the value of CFM changes.  To better clarify these conditions, compressor manufacturers decided to add terms with definitions.

The first letter in front of CFM above now defines the conditions in which the volumetric air flow is being measured.  This is important for comparing pneumatic components or for properly sizing air compressors and pneumatic systems. Volume is measured in three areas: temperature, pressure, and relative humidity as seen in the Ideal Gas Law.

Equation 1:

V = n * R * T / P

V – Volume

n – Number of molecules of gas

R – Universal Gas Constant

T – Absolute Temperature

P – Absolute Pressure

The volume of air can change in reference to pressure, temperature, and the number of molecules.  Where is the relative humidity?  This would be referenced in the “n” term.  The more water vapor, or higher RH values, the fewer molecules of air are in a given volume.

SCFM is the most commonly used term, and it can be the most confusing.  The idea of this volumetric air flow is to set a reference point for comparisons.  So, no matter the pressure, temperature, or relative humidity, the volumetric air flows can be compared to each other at one reference point.  There have been many debates about an appropriate standard temperature and pressure, or STP.  But as long as you use the same reference point, then you can still compare the results.  In this blog, I will be using the Compressed Air and Gas Institute, CAGI, reference where the “Standard” condition is at 14.5 PSIA, 68oF, and 0% RH.  Since we have the reference point, we still need to know the actual conditions.  As an example, it is like having a location for a restaurant as a reference, but if you do not know your current location, you cannot find it.   Similarly, we are “moving” the air from one condition to a reference or “Standard” condition.  We will need to know where the air began in order to reach that reference point.  We will talk more about this later in this blog.

ACFM is the volumetric air flow under actual conditions.  This is actually the “true” flow rate.  Even though this term is hardly used, there are reasons why we will need to know this value.  We use the ACFM value to calculate velocities and pressure drops in a system.  We can also correlate between SCFM and ACFM:

Equation 2:

ACFM = SCFM * [Pstd / (Pact – Psat Φ)] * (Tact / Tstd)

Where:

ACFM = Actual Cubic Feet per Minute
SCFM = Standard Cubic Feet per Minute
Pstd = standard absolute air pressure (14.5 psia)
Pact = absolute pressure at the actual level (psia)
Psat = saturation pressure at the actual temperature (psi)
Φ = Actual relative humidity
Tact = Actual ambient air temperature (oR) or (oF + 460)
Tstd = Standard temperature (528oR) or (68oF + 460)

ICFM, or Inlet Cubic Feet per Minute, is one of the newer terms in the history of air compressors.  This is where devices are added to the inlet of an air compressor, affecting the flow conditions.  If you have a blower on the inlet of an air compressor, the volumetric flow rate changes as the pressure and temperature rise at the “Inlet”.  If an intake filter is used, then the pressure drop will decrease the incoming pressure at the “Inlet”.  These devices that affect the volumetric flow rate of an air compressor should be considered.  Equation 3 shows the relationship between ACFM and ICFM:

Equation 3:

ICFM = ACFM * (Pact / Pf) * (Tf / Tact)

Where:

ICFM = Inlet Cubic Feet Per Minute

ACFM = Actual Cubic Feet per Minute

Pact = absolute pressure at the actual level (psia)

Pf  = Pressure after filter or inlet equipment (PSIA)

Tf = Temperature after filter or inlet equipment (°R)

Tact = Actual ambient air temperature (oR)

To expand on my explanation above about SCFM and ACFM, a technical question comes up often about the pressure when using SCFM.  The reference point of 14.5 PSIA is in the definition of SCFM.  Remember, this is only a reference point.  The starting location is actually needed.  This would be the ACFM value where the air values are true and actual.  As an example, two air nozzles are rated for 60 SCFM.  An EXAIR Super Air Nozzle, model 1106, is cataloged at 80 PSIG, and a competitor is cataloged at 60 PSIG.  By comparison, they look like they use the same amount of compressed air, but do they actually?  To simplify Equation 2 above, we can compare the two nozzles at the same temperature, 68oF, and 0% RH. This equation can be reduced to:

Equation 4:

ACFM = SCFM * 14.5 / (P + 14.5)

@60 PSIG Competitor:

ACFM = 60 SCFM * 14.5 PSIA/ (60 PSIG + 14.5 PSIA)

= 11.7 ACFM

@80 PSIG EXAIR Super Air Nozzle:

ACFM = 60 SCFM * 14.5 PSIA / (80 PSIG + 14.5PSIA)

= 9.2 ACFM

Even though the SCFM rating is the same but at two different pressures, the actual flow shows that you are using 21% more compressed air with the competitive nozzle. 

Another example would be for sizing an air compressor.  Since air compressors are rated at sea level (14.5 PSIA), 68oF and 0% RH, what happens if you are in Denver?  A manufacturing company was looking for a 500 SCFM air compressor to run their plant.  They were located at 1,000 feet above sea level with a site temperature of 85oF and a relative humidity of 60%.  Since they were not at the standard conditions, we can calculate the ACFM to properly size the air compressor.  At 1,000 feet above sea level, the atmospheric pressure is 14.2 PSIA.  The saturation pressure at 85oF is 0.595 PSIA.  From Equation 2, we can calculate the ACFM.

ACFM = SCFM * [Pstd / (Pact – Psat Φ)] * (Tact / Tstd)

ACFM = 500 SCFM * [14.5 / (14.2 – 0.595 * 60%)] * (85oF + 460) / (68oF + 460)

ACFM = 500 SCFM * 1.0474 * 1.0322

ACFM = 540

For this manufacturing plant, they will need to increase the capacity to 540 SCFM to run their 500 SCFM pneumatic system at their location.  If they had to add any inlet equipment to the air compressor, then we could use the ICFM equation, Equation 3, to provide the proper volume of compressed air.

When it comes to rating compressed air products or air compressors, always ask about the conditions for the pressure, temperature and RH.  Your local compressor dealer can help you in selecting the proper unit.  The more you know about volumetric flow rates, the better decision that you can make in selecting the correct product.  If you need any help with saving compressed air on your point-of-use blow-off devices, you can contact an Application Engineer at EXAIR.  We will be happy to help you with our efficient and safe engineered products. 

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Photo: Air sign by Barney MossCreative Commons 2.0

Robert Boyle – Real Men of Genius!

EXAIR presents, Real Men of Genius. Today we salute you Mr. Robert Boyle, highly regarded as one of the founders of modern chemistry! Your law perfectly describes the inversely proportional relationship between the absolute pressure and volume of a gas, if the temperature is kept constant within a closed system. (Make sure you go back and read that in the old Budweiser song tune!!)

But back on a serious note, Robert Boyle is a man who changed the way we look at scientific research. From the Scientific Method to the laws that govern gases, Robert Boyle was able to change the very way we look at life and solve our problems. One could say that Robert Boyle didn’t really have what you would call a humble beginning; he was born in January 1627 to the 1st Earl of Cork, Richard Boyle and his wife Catherine Fenton at Lismore Castle in Ireland. When he was only 8 years of age, he was sent off to Eton College in order to study under a private tutor. In 1641, Robert would spend the winter in Florence, Italy studying the “paradoxes of the great star-gazer” Galileo Galilei.

Starting in mid-1644, Robert would build his residence in Dorset, England, where he conducted many experiments and from then devote his life to research. In 1654, Boyle would move to Oxford from Ireland in order to further pursue his studies in chemistry. It was here in 1657 that he would read about Otto von Guericke’s air pump, and would set out to improve the system along with Robert Hooke. In 1659, the “Pneumatic Engine” would be completed, and he began a series of experiments on the properties of air. He would further go on to coin the term factitious airs, which is a term used to describe synthetic gases after isolating what is now understood to be hydrogen.

Boyle’s Law

Though he was primarily interested in chemistry, one of Boyle’s most famous discoveries was what is now known as the first of the gas laws, rightfully named Boyles’s Law.  Boyle’s Law defines the relationship between pressure and volume in a closed area given the mass of an ideal gas. Boyle and his assistant Robert Hooke used a closed J-Shaped tube and poured mercury in from the open side, forcing the air on the other side to contract under the pressure. After repeating this using several different amounts of mercury, Boyle deducted that the pressure of a gas is inversely proportional to the volume occupied by it.

Boyles law apparatus
Boyles law apparatus is used to visualize the relationship between the absolute pressure and volume of a gas.

Robert Boyle passed away on December 31st, 1691, and from his work, EXAIR uses the pressure and volume of compressed air for our Intelligent Compressed Air® Products to make them efficient, safe, and effective.  If you would like to speak more about how EXAIR can benefit your pneumatic system, one of our Application Engineers can help you determine the best solution.

Jordan Shouse
Application Engineer
Email: jordanshouse@exair.com
Twitter: @EXAIR_JS

Robert Boyle image courtesy of Skara KommunCreative Commons License

Boyles law apparatus image courtesy of Siyavula Education, Creative Commons License

Standard Temperature and Pressure: What is STP?

When it comes to volumetric flow rates, you probably noticed the prefix of an “S” for SCFM and SLPM, or an “N” for NM3/hr.  The “S” prefix is for Standard conditions, and the “N” prefix is for Normal conditions.  For practical reasons, they are the same thing.  What does this mean? 

Let’s look at the Ideal Gas Law in Equation 1:

Equation 1:

PV = nRT 

P – Pressure

V – Volume

n – No. of moles

R – Ideal Gas constant

T – temperature

Since air is compressible, it will react in different ways.  If we keep the volume the same and lower the temperature, the gas pressure will go down.  If we keep the temperature the same and decrease the volume, the gas pressure will go up.  If we go to a higher elevation, the number of moles is reduced, which will lower the gas pressure.  With the different degrees of changes, it is difficult to compare.  So, organizations decided to place a standard on these conditions to help compare results.  The definition is referred to as STP, or Standard Temperature and Pressure. 

In most cases, the Standard Temperature and Pressure is set at 20oC and 1 atm (1.013 bar).  If we transition all pneumatic units to this condition, we can then compare the results for each product.  We can determine which units actually use less compressed air or have higher forces.  Or if we decide to use a different STP, we can do that as well as long as we use the same temperature and pressure. 

I like to think of it like an air-filled balloon floating on top of the water.  This would be the “Standard” or “Normal” condition.  As you take the balloon into deeper water, more pressure is applied to the balloon, and the volume will decrease.  This is because air is compressible.  The balloon still has the same amount of air by weight (as the volume decreases, the density increases).  If you return to the surface, the balloon will expand back to the original size.  When doing comparisons, we need to be in the same condition, or for the balloon example, it will look like the balloon will need less air at lower depths than at the surface.   

The reason for this explanation is that some competitors like to use lower pressures to rate their products.  As an example, Competitor A rates their nozzles at 5 bar (72.5 psig).  EXAIR uses 5.5 bar (80 psig) for most of our products.  By comparison, we cannot say if one unit uses more or less compressed air unless we set them at the same conditions.  The best place to compare is at a Standard Temperature and Pressure, or STP.   I go into more detail in my blog about air flows with “CFM, ICFM, ACFM, SCFM: Volumetric Flow Rates Explained”.  EXAIR offers Super Air Knives, Super Air Nozzles, and Super Air Amplifiers to efficiently blow compressed air.  So, when a company states a compressed air flow, verify the pressure and temperature at which they recorded that information.  It will help you to be more in tune with what you are getting (allow for an apples to apples comparison). If you need any help in doing comparisons, an Application Engineer at EXAIR will be happy to assist you. 

John Ball
Application Engineer

Email: johnball@exair.com
Twitter: @EXAIR_jb

Photo:  balloon helium air flying bright by stuxPixabay license

CFM, ICFM, ACFM, SCFM: Volumetric Flow Rates Explained

Flow rate is the quantity of material that moves over a period of time.  Generally, the quantity of material can be expressed as a mass or a volume.  For example, mass flow rates are generally in units of pounds per minute (lbs./min) or kilograms per hour (Kg/hr).  Volumetric flow rates are stated in cubic feet per minute (CFM) or liters per hour (LPH).  The trick begins when volumetric flow rates are used for a compressible gas.  In this blog, I will go over the various acronyms and the reasons behind them.

What acronyms will be covered?

CFM – Cubic Feet per Minute

SCFM – Standard Cubic Feet per Minute

ACFM – Actual Cubic Feet per Minute

ICFM – Inlet Cubic Feet per Minute

The volumetric component of the flow rate above is CFM or Cubic Feet per Minute.  This term is commonly used in rating air compressors and pneumatic equipment.  From their history, they would calculate the volume of air being drawn into the air compressor by the size of cylinder.  With the rotations per minute of the motor, RPM, they could calculate the volumetric flow rate.  As conditions change like altitude, temperature, and relative humidity, the value of CFM changes.  To better clarify these conditions, compressor manufacturers decided to add terms with definition.  (For your information, air compressors still use CFM as a unit of air flow, but now this is defined at standard temperature and pressure).

The first letter in front of CFM above now defines the conditions in which the volumetric air flow is being measured.  This is important for comparing pneumatic components or for properly sizing pneumatic systems. Volume is measured by three areas: temperature, pressure, and relative humidity as seen in the Ideal Gas Law.

Equation 1:

V = n * R * T / P

V – Volume

n – Number of molecules of gas

R – Universal Gas Constant

T – Absolute Temperature

P – Absolute Pressure

The volume of air can change in reference to pressure, temperature, and the number of molecules.  Where is the relative humidity?  This would be referenced in the “n” term.  The more water vapor, or higher RH values, the less molecules of air is in a given volume.

SCFM is the most commonly used term, and it can be the most confusing.  The idea of this volumetric air flow is to set a reference point for comparisons.  So, no matter the pressure, temperature, or relative humidity; the volumetric air flows can be compared to each other at one reference point.  There have been many debates about an appropriate standard temperature and pressure, or STP.  But as long as you use the same reference point, then you can still compare the results.  In this blog, I will be using the Compressed Air and Gas Institute, CAGI, reference where the “Standard” condition is at 14.5 PSIA, 68oF, and 0% RH.  Since we have the reference point, we still need to know the actual conditions.  As an example, it is like having a location for a restaurant as a reference, but if you do not know your current location, you cannot reach it.   Similarly, we are “moving” the air from one condition to a reference or “Standard” condition.  We will need to know where the air began in order to reach that reference point.  We will talk more about this later in this blog.

ACFM is the volumetric air flow under actual conditions.  This is actually the “true” flow rate.  Even though this term is hardly used, there are reasons why we will need to know this value.  We can resize an air compressor that is not at “Standard” conditions, and we can use this value to calculate velocities and pressure drop in a system.  We can correlate between SCFM and ACFM:

Equation 2:

ACFM = SCFM * [Pstd / (Pact – Psat Φ)] * (Tact / Tstd)

Where:

ACFM = Actual Cubic Feet per Minute
SCFM = Standard Cubic Feet per Minute
Pstd = standard absolute air pressure (psia)
Pact = absolute pressure at the actual level (psia)
Psat = saturation pressure at the actual temperature (psi)
Φ = Actual relative humidity
Tact = Actual ambient air temperature (oR) or (oF + 460)
Tstd = Standard temperature (oR) or (oF + 460)

ICFM, or Inlet Cubic Feet per Minute, is one of the newest terms in the history of air compressors.  This is where devices are added to the inlet of an air compressor, affecting the flow conditions.  If you have a blower on the inlet of an air compressor, the volumetric flow rate changes as the pressure and temperature rises at the “Inlet”.  If an intake filter is used, then the pressure drop will decrease the incoming pressure at the “Inlet”.  These devices that affect the volumetric flow rate for an air compressor should be considered.  Equation 3 shows the relationship to ACFM and ICFM:

Equation 3:

ICFM = ACFM * (Pact / Pf) * (Tf / Tact)

Where:

ICFM = Inlet Cubic Feet Per Minute

ACFM = Actual Cubic Feet per Minute

Pf  = Pressure after filter or inlet equipment (PSIA)

Tf = Temperature after filter or inlet equipment (°R)

To expand on my explanation above about SCFM and ACFM, a technical question comes up often about the pressure when using SCFM.  The reference point of 14.5 PSIA is in the definition of SCFM.  Remember, this is only a reference point.  The starting location is actually needed.  This would be the ACFM value where the air values are true and actual.  As an example, two air nozzles are rated for 60 SCFM.  An EXAIR Super Air Nozzle, model 1106, is cataloged at 80 PSIG, and a competitor is cataloged at 60 PSIG.  By comparison, they look like they use the same amount of compressed air, but do they actually?  To simplify Equation 2 above, we can compare the two nozzles at the same temperature, 68oF, and 0% RH. This equation can be reduced to:

Equation 4:

ACFM = SCFM * 14.5 / (P + 14.5)

@60 PSIG Competitor:

ACFM = 60 SCFM * 14.5 PSIA/ (60 PSIG + 14.5 PSIA)

= 11.7 ACFM

@80 PSIG EXAIR Super Air Nozzle:

ACFM = 60 SCFM * 14.5 PSIA / (80 PSIG + 14.5PSIA)

= 9.2 ACFM

Even though the SCFM rating is the same but at two different pressures, the actual flow shows that you are using 21% more compressed air with the competitive nozzle. 

Another example would be for sizing an air compressor.  Since air compressors are rated at sea level (14.5 PSIA), 68oF and 0% RH, what happens if you are in Denver?  A manufacturing company was needing a 500 SCFM air compressor to run their plant.  They were located at 1,000 feet above sea level with a site temperature of 85oF and a relative humidity of 60%.  Since they were not at the standard conditions, we can calculate the ACFM to properly size the air compressor.  The atmospheric pressure at 1,000 feet was 14.2 PSIG.  The saturation pressure at 85oF is 0.595 PSIA.  From Equation 2, we can calculate the ACFM.

ACFM = SCFM * [Pstd / (Pact – Psat Φ)] * (Tact / Tstd)

ACFM = 500 SCFM * [14.5 / (14.2 – 0.595 * 60%)] * [(85oF + 460) / (68oF + 460)]

ACFM = 500 SCFM * 1.0474 * 1.0322

ACFM = 540

For this manufacturing plant, they will need to increase the capacity to 540 SCFM to run their 500 SCFM pneumatic system at their location.   

When it comes to rating compressed air products or air compressors, always ask the conditions of the pressure, temperature and RH.  The more you know about volumetric flow rates, the better decision that you can make in selecting the correct product.  If you need any help in selecting point-of-use blow-off devices, you can contact an Application Engineer at EXAIR.  We will be happy to help you. 

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Photo: Air sign by Barney MossCreative Commons 2.0