Volumetric Flow Rates: CFM, ICFM, ACFM, SCFM.  What Does it All Mean?

Flow rate is the quantity of material that moves over a period of time.  Generally, the quantity of material can be expressed as a mass or a volume.  For example, mass flow rates are generally in units of pounds per minute (lbs./min) or kilograms per hour (Kg/hr).  Volumetric flow rates are stated in cubic feet per minute (CFM) or liters per hour (LPH).  The trick begins when volumetric flow rates are used for a compressible gas.  In this blog, I will cover the various acronyms and the reasons behind them.

What acronyms will be covered?

CFM – Cubic Feet per Minute

SCFM – Standard Cubic Feet per Minute

ACFM – Actual Cubic Feet per Minute

ICFM – Inlet Cubic Feet per Minute

The volumetric component of the flow rate above is CFM or Cubic Feet per Minute.  This term is commonly used in rating air compressors and pneumatic equipment.  From their history, they would calculate the volume of air being drawn into the air compressor by the size of cylinder.  With the rotations per minute of the motor, RPM, they could calculate the volumetric flow rate.  As conditions change, like altitude, temperature, and relative humidity, the value of CFM changes.  To better clarify these conditions, compressor manufacturers decided to add terms with definitions.

The first letter in front of CFM above now defines the conditions in which the volumetric air flow is being measured.  This is important for comparing pneumatic components or for properly sizing air compressors and pneumatic systems. Volume is measured in three areas: temperature, pressure, and relative humidity as seen in the Ideal Gas Law.

Equation 1:

V = n * R * T / P

V – Volume

n – Number of molecules of gas

R – Universal Gas Constant

T – Absolute Temperature

P – Absolute Pressure

The volume of air can change in reference to pressure, temperature, and the number of molecules.  Where is the relative humidity?  This would be referenced in the “n” term.  The more water vapor, or higher RH values, the fewer molecules of air are in a given volume.

SCFM is the most commonly used term, and it can be the most confusing.  The idea of this volumetric air flow is to set a reference point for comparisons.  So, no matter the pressure, temperature, or relative humidity, the volumetric air flows can be compared to each other at one reference point.  There have been many debates about an appropriate standard temperature and pressure, or STP.  But as long as you use the same reference point, then you can still compare the results.  In this blog, I will be using the Compressed Air and Gas Institute, CAGI, reference where the “Standard” condition is at 14.5 PSIA, 68oF, and 0% RH.  Since we have the reference point, we still need to know the actual conditions.  As an example, it is like having a location for a restaurant as a reference, but if you do not know your current location, you cannot find it.   Similarly, we are “moving” the air from one condition to a reference or “Standard” condition.  We will need to know where the air began in order to reach that reference point.  We will talk more about this later in this blog.

ACFM is the volumetric air flow under actual conditions.  This is actually the “true” flow rate.  Even though this term is hardly used, there are reasons why we will need to know this value.  We use the ACFM value to calculate velocities and pressure drops in a system.  We can also correlate between SCFM and ACFM:

Equation 2:

ACFM = SCFM * [Pstd / (Pact – Psat Φ)] * (Tact / Tstd)

Where:

ACFM = Actual Cubic Feet per Minute
SCFM = Standard Cubic Feet per Minute
Pstd = standard absolute air pressure (14.5 psia)
Pact = absolute pressure at the actual level (psia)
Psat = saturation pressure at the actual temperature (psi)
Φ = Actual relative humidity
Tact = Actual ambient air temperature (oR) or (oF + 460)
Tstd = Standard temperature (528oR) or (68oF + 460)

ICFM, or Inlet Cubic Feet per Minute, is one of the newer terms in the history of air compressors.  This is where devices are added to the inlet of an air compressor, affecting the flow conditions.  If you have a blower on the inlet of an air compressor, the volumetric flow rate changes as the pressure and temperature rise at the “Inlet”.  If an intake filter is used, then the pressure drop will decrease the incoming pressure at the “Inlet”.  These devices that affect the volumetric flow rate of an air compressor should be considered.  Equation 3 shows the relationship between ACFM and ICFM:

Equation 3:

ICFM = ACFM * (Pact / Pf) * (Tf / Tact)

Where:

ICFM = Inlet Cubic Feet Per Minute

ACFM = Actual Cubic Feet per Minute

Pact = absolute pressure at the actual level (psia)

Pf  = Pressure after filter or inlet equipment (PSIA)

Tf = Temperature after filter or inlet equipment (°R)

Tact = Actual ambient air temperature (oR)

To expand on my explanation above about SCFM and ACFM, a technical question comes up often about the pressure when using SCFM.  The reference point of 14.5 PSIA is in the definition of SCFM.  Remember, this is only a reference point.  The starting location is actually needed.  This would be the ACFM value where the air values are true and actual.  As an example, two air nozzles are rated for 60 SCFM.  An EXAIR Super Air Nozzle, model 1106, is cataloged at 80 PSIG, and a competitor is cataloged at 60 PSIG.  By comparison, they look like they use the same amount of compressed air, but do they actually?  To simplify Equation 2 above, we can compare the two nozzles at the same temperature, 68oF, and 0% RH. This equation can be reduced to:

Equation 4:

ACFM = SCFM * 14.5 / (P + 14.5)

@60 PSIG Competitor:

ACFM = 60 SCFM * 14.5 PSIA/ (60 PSIG + 14.5 PSIA)

= 11.7 ACFM

@80 PSIG EXAIR Super Air Nozzle:

ACFM = 60 SCFM * 14.5 PSIA / (80 PSIG + 14.5PSIA)

= 9.2 ACFM

Even though the SCFM rating is the same but at two different pressures, the actual flow shows that you are using 21% more compressed air with the competitive nozzle. 

Another example would be for sizing an air compressor.  Since air compressors are rated at sea level (14.5 PSIA), 68oF and 0% RH, what happens if you are in Denver?  A manufacturing company was looking for a 500 SCFM air compressor to run their plant.  They were located at 1,000 feet above sea level with a site temperature of 85oF and a relative humidity of 60%.  Since they were not at the standard conditions, we can calculate the ACFM to properly size the air compressor.  At 1,000 feet above sea level, the atmospheric pressure is 14.2 PSIA.  The saturation pressure at 85oF is 0.595 PSIA.  From Equation 2, we can calculate the ACFM.

ACFM = SCFM * [Pstd / (Pact – Psat Φ)] * (Tact / Tstd)

ACFM = 500 SCFM * [14.5 / (14.2 – 0.595 * 60%)] * (85oF + 460) / (68oF + 460)

ACFM = 500 SCFM * 1.0474 * 1.0322

ACFM = 540

For this manufacturing plant, they will need to increase the capacity to 540 SCFM to run their 500 SCFM pneumatic system at their location.  If they had to add any inlet equipment to the air compressor, then we could use the ICFM equation, Equation 3, to provide the proper volume of compressed air.

When it comes to rating compressed air products or air compressors, always ask about the conditions for the pressure, temperature and RH.  Your local compressor dealer can help you in selecting the proper unit.  The more you know about volumetric flow rates, the better decision that you can make in selecting the correct product.  If you need any help with saving compressed air on your point-of-use blow-off devices, you can contact an Application Engineer at EXAIR.  We will be happy to help you with our efficient and safe engineered products. 

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Photo: Air sign by Barney MossCreative Commons 2.0

Plumb it Right for Full Performance!

Many times when we provide the air consumption of an EXAIR product, we get a response like…. “I’ve got plenty of pressure, we run at around 100 PSIG”. While having the correct pressure available is important, it doesn’t make up for the volume requirement or SCFM (Standard Cubic Feet per Minute) needed to maintain that pressure. We commonly reference trying to supply water to a fire hose with a garden hose, it is the same principle, in regards to compressed air.

When looking to maintain an efficient compressed air system, it’s important that you use properly sized supply lines and fittings to  support the air demand (SCFM) of the point-of-use device. The smaller the ID and the longer the length of air supply line, it becomes more difficult for the air to travel through the system. Undersized supply lines or piping can sometimes be the biggest culprit in a compressed air system as they can lead to severe pressure drops or the loss of pressure from the compressor to the end use product.

Take for example our 18″ Super Air Knife. An 18″ Super Air Knife will consume 52.2 SCFM at 80 PSIG. We recommend using 1/2″ Schedule 40 pipe up to 10′ or 3/4″ pipe up to 50′. The reason you need to increase the pipe size after 10′ of run is that 1/2″ pipe can flow close to 100 SCFM up to 10′ but for a 50′ length it can only flow 42 SCFM. On the other hand, 3/4″ pipe is able to flow 100 SCFM up to 50′ so this will allow you to carry the volume needed to the inlet of the knife, without losing pressure through the line.

Pipe size chart for the Super Air Knife

Another problem area is using restrictive fittings, like quick disconnects. While this may be useful with common everyday pneumatic tools, like an impact wrench or nail gun, they can severely limit the volumetric flow to a device requiring more air , like a longer length air knife.

1/4″ Quick Connect

For example, looking at the above 1/4″ quick disconnect, the ID of the fitting is much smaller than the NPT connection size. In this case, it is measuring close to .192″. If you were using a device like our Super Air Knife that features 1/4″ FNPT inlets, even though you are providing the correct thread size, the small inside diameter of the quick disconnect causes too much of a restriction for the volume (SCFM) required to properly support the knife, resulting in a pressure drop through the line, reducing the overall performance.

If you have any questions about compressed air applications or supply lines, please contact one of our application engineers for assistance.

Jordan Shouse
Application Engineer

Send me an Email
Find us on the Web 
Like us on Facebook
Twitter: @EXAIR_JS

Compressor Intake – Air Flows 

Flow rate is the quantity of material that is moved per unit of time.  Generally, the quantity of material can be expressed as a mass or a volume.  For example, mass flow rates are in units of pounds per minute or kilograms per hour.  Volumetric flow rates are stated in cubic feet per minute, CFM, or liters per hour, LPH.  The trick begins when volumetric flow rates are used with compressible gases.  In this blog, I will go over the various acronyms and the reasons behind them.

What acronyms will be covered?

CFM – Cubic Feet per Minute

SCFM – Standard Cubic Feet per Minute

ACFM – Actual Cubic Feet per Minute

ICFM – Inlet Cubic Feet per Minute

The volumetric component of the flow rate is CFM or Cubic Feet per Minute.  This term is commonly used for rating air compressors.  From the history of air compressors, they could calculate the volume of air being drawn into the air compressor by the size of the cylinder.  With the volume of the compression chamber and the rotations per minute of the motor, RPM, they could calculate the volumetric air flows.  As conditions change like altitude, temperature, and relative humidity, the volumetric value of CFM changes.  To better clarify these conditions, compressor manufacturers have decided to add terms with a definition.  (For your information, air compressors still use CFM as a unit of air flow, but now this is defined at standard temperature and pressure).

The first letter in front of CFM above now defines the conditions in which volumetric air flow is being measured.  This is important for comparing pneumatic components or for properly sizing pneumatic systems.  Volume is measured within three areas; temperature, pressure, and relative humidity.  We can see this in the Ideal Gas Law, reference Equation 1.

Equation 1:

P * V = n * R * T

Where:

P – Absolute Pressure

V – Volume

n – Number of molecules of gas

R – Universal Gas Constant

T – Absolute Temperature

The volume of air can change in reference to pressure, temperature, and the number of molecules.  You may ask where the relative humidity is?  This would be referenced in the “n” term.  The more water vapor, or higher RH values, the less molecules of air are in a given volume.

SCFM is the most commonly used term, and it can be the most confusing.  The idea behind this volumetric air flow is to set a reference point for comparisons.  So, no matter the pressure, temperature, or relative humidity; the volumetric air flows can be compared to each other at that reference point.  There have been many debates about an appropriate standard temperature and pressure, or STP.  But as long as you use the same reference point, then you can still compare the results.  In this blog, I will be using the Compressed Air and Gas Institute, CAGI, reference where the “Standard” condition is at 14.5 PSIA, 68 o F, and 0% RH.  Since we have a reference point, we still need to know the actual conditions for comparison.  It is like having the location of a restaurant as a reference, but if you do not know your current location, you cannot move toward it.   Similarly, we are “moving” the air from its actual condition to a reference or “Standard” condition.  If we do not know the actual state where the air began, then we cannot “move” toward that reference point.  We will talk more about this later in this blog.

ACFM is the volumetric air flow under actual conditions.  This is actually the “true” flow rate.  Even though this term is hardly used, there are reasons why we will need to know this value.  We can size an air compressor that is not at “Standard” conditions, and we can use this value to calculate velocity and pressure drop in a pneumatic system.  We can correlate between SCFM and ACFM with Equation 2.

Equation 2:

ACFM = SCFM * [Pstd / (Pact – Psat * Φ)] * (Tact / Tstd)

Where:

ACFM – Actual Cubic Feet per Minute

SCFM – Standard Cubic Feet per Minute

Pstd – standard absolute air pressure (PSIA)

Pact – absolute pressure at the actual level (PSIA)

Psat – saturation pressure at the actual temperature (PSI)

Φ – Actual relative humidity (%)

Tact – Actual ambient air temperature (oR)

Tstd – Standard temperature (oR)

ICFM is one of the newest terms in the history of air compressors.  This is where devices are added to the inlet of an air compressor, affecting flow conditions.  If you have a blower on the inlet of an air compressor, the volumetric flow rate changes as the pressure and temperature rises at the “Inlet”.  If a filter is used, then the pressure drop will decrease the incoming pressure at the “Inlet”.  These devices that affect the volumetric flow rate for an air compressor should be considered.  The equation to relate ACFM to ICFM is Equation 3.

Equation 3:

ICFM = ACFM * (Pact / Pf) * (Tf / Tact)

Where:

ICFM – Inlet Cubic Feet Per Minute

ACFM – Actual Cubic Feet per Minute

Pact – absolute pressure at the actual level (PSIA)

Pf – Pressure after filter or inlet equipment (PSIA)

Tact – Actual ambient air temperature (oR)

Tf – Temperature after filter or inlet equipment (°R)

To expand on my explanation above about SCFM and ACFM, a technical question is asked often about the pressure when using SCFM.  The reference point of 14.5 PSIA is in the definition of the term for SCFM.  Remember, this is only a reference point.  The starting location is also needed as it gives us the ACFM value where the air values are true and actual.  Then we can make a comparison of actual air usage. 

As an example, let’s look at two air nozzles that are rated at the same air flow; 60 SCFM.  The EXAIR Super Air Nozzle, model 1106, is cataloged at 60 SCFM at 80 PSIG, and a competitor is cataloged at 60 SCFM at 72 PSIG.  By comparison, they look like they use the same amount of compressed air, but actually they do not.  To simplify Equation 2, we can compare the two nozzles at the same temperature and RH at 68 oF and 0% RH respectively.  This equation can be reduced to form Equation 4.

Equation 4:

ACFM = SCFM * 14.5 / (P + 14.5)

@72 PSIG Competitor:

ACFM = 60 SCFM * 14.5 PSIA/ (72 PSIG + 14.5 PSIA)

= 10.1 ACFM

@80 PSIG EXAIR Super Air Nozzle:

ACFM = 60 SCFM * 14.5 PSIA / (80 PSIG + 14.5PSIA)

= 9.2 ACFM

Even though the SCFM is the same amount, you are actually using 10% more air with the competitive nozzle that was reported at 60 PSIG.  So, when it comes to rating pneumatic products, improving efficiency, and saving money; always determine the pressure that you are at.  The more you know about volumetric flow rates, the better decision that you can make.  If you need more information, you can always contact our Application Engineers at EXAIR.  We will be happy to assist.

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Photo: Compressor equipment by terimakasih0Pixabay license

Friction Loss – Pressure Drops – Fitting Restrictions – Why Compressed Air Plumbing Matters

Over the weekend I was working on a car in my driveway and I needed a large volume of air at the far end of the car to try and unplug a clogged sunroof drain line.  Rather than trying to move the car while it was mostly taken apart, I just hooked up another air line extension and started to go to the drain.   Even knowing what I know as an EXAIR Application Engineer about lengths of tubing, air restriction, and fitting restrictions, I went ahead with the quick and easy “fix”.

An example of pressure drop from a compressed air quick disconnect.

I grabbed another 30′ – 3/8″ i.d. air line with 1/4″ quick disconnects (see why this is wrong with this blog) on both end, rather than getting out the 50′ long 1/2″ i.d. air line that I have with proper fittings that then reduce down to a 1/4″NPT at the end to tie into most of my air tools. By doing so I ended up hooking up a Safety Air Gun which then gave a very light puff of air into the tube and the clog in the line went nowhere.  As a matter of fact, it was almost like it laughed because the tubing vibrated as if the clog said, “Pfft I am going nowhere.”

I then, stepped back and evaluated what I had done in a rush to try and get a job done rather than taking the extra five minutes to get the proper air line to do the job.   I then spent 10 minutes putting that hose up and getting out the correct hose.  Then, with a whoosh and a thud the clog was launched into my yard from the clogged drain port and I finished the repairs.

If only I had watched Russ Bowman’s spectacular video on Proper Compressed Air Supply Plumbing the day before. Rather than wasting time with the quick “fix” that cost me more time and didn’t fix anything I should have taken a little more time up front to verify I had properly sized my lines for the job at hand.

If you would like to discuss compressed air plumbing, appropriate line sizes, or insufficient flow on your compressed air system, please contact an EXAIR Application Engineer.

Brian Farno
Application Engineer
BrianFarno@EXAIR.com
@EXAIR_BF