Wet Receiver Tanks: Why Use Them, and How to Size Them

9500-60 Receiver Tank

Compressed air is used to operate pneumatic systems within a facility, and it can be separated into three categories; the supply side, the demand side, and the distribution system.  The supply side will include the air compressor, after-cooler, dryer, and receiver tank.  It produces and treats the compressed air before it travels into the distribution system.  They are generally located in a compressor room somewhere in the corner of the plant.  In this blog, I would like to cover the wet receiver tank that is used as part of the supply side.

What is a receiver tank?  I like to compare pneumatic systems to electrical systems.  The receiver tanks store the pneumatic energy produced by an air compressor like a capacitor stores electrical energy.  The reason for this is to have a ready source of energy to increase efficiency and speed through the ebbs and flows of demand. 

A wet receiver, like the name imparts, is positioned downstream of the air compressor but before the air dryer.  A dry receiver would be located after the air dryer.  Some systems will utilize both types.  With the wet receiver, you remove some of the load of water that reaches the air dryer, which helps to make the air dryers more efficient and extends the life cycle.  When ambient air is compressed, the humidity will condense, making water.  Also, as air cools in the wet receiver, water vapor turns into liquid condensate—often mixed with traces of oil and dirt from the air compressor. To get rid of the contaminants, a condensate drain will be required to get rid of this unwanted liquid.

For sizing the wet receiver, it is roughly 1 to 3 gallons per cfm for a compressor.  So, for a 100 SCFM air compressor, you should have a tank that is roughly 100 to 300 gallons.  If you have large fluctuations on the demand side, you can also use Equation 1 below to calculate the minimum tank volume.  If you are using wet and dry receiver tanks in your system, you can divide the total volume.  The wet receiver tank should be one-third of the volume, and the dry receiver tank should be two-thirds of the volume. 

Equation 1:

V = T * C * (Pa) / (P1-P2)

Where:

V – Volume of receiver tank (cubic feet)

T – Time interval between pressure limits (minutes)

C – Air demand for system (cubic feet per minute)

Pa – Absolute atmospheric pressure (PSIA)

P1 – Upper Pressure limit (PSIG)

P2 – Lower Pressure limit (PSIG)

Compressed air systems are the backbone of countless industries and operations.  But behind the scenes, components like the wet receiver and condensate drain play pivotal roles in ensuring these systems deliver clean, reliable air.  If you wish to discuss more ways to optimize your compressed air system, EXAIR has Application Engineers that would like to help you. 

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Intelligent Compressed Air®: Compressor Motors And Controls

Use of compressed air has gone hand in hand with manufacturing for centuries. From manually operated bellows devices that stoked fires to generate the high temperatures needed for forging metals in ancient times, to the massive steam or oil driven compressors used in the 1800’s on projects like the Mont Cenis Tunnel drills, to the sophisticated electric-powered compressors used widely across modern industry, compressed air has actually been “the fourth utility” longer than the other three (electricity, gas, and water) have been in existence.

Diesel & gas powered compressors offer advantages like higher power ratings, portability, and freedom from reliance on local electric power grids, but most air compressors in industrial use are powered by electric motors. They’re plentiful, reliable, and easily adaptable to a range of control schemes that offer efficient operation across a wide variety of operations.

Which control method is right for you will depend on a number of factors specific to your operation. Here’s a brief run-down that may help you narrow down the selection:

  • Compressors in smaller facilities that supply intermittent loads like air guns, paint sprayers, tire inflators, etc. (like the one shown on the right) are oftentimes controlled via Start/Stop. This turns the compressor motor on and off, in response to a pressure signal. This is the simplest, least expensive method, and is just fine for smaller reciprocating compressors that aren’t adversely affected by cycling on & off.
  • Some compressors ARE adversely affected by Start/Stop control…like rotary screw models. These take a finite amount of time to start back up, which could allow header pressure to drop below usable levels. If they cycle too often, heat from the starting current can build up & overheat the motor. If that’s not bad enough, the screw elements & bearings of the compressor itself are oil lubricated…every time they start up, there’s a finite amount of time where metal-to-metal contact occurs before the oil flow is providing rated lubrication. With Load/Unload control, the motor turns continuously, while a valve on the intake of the compressor is cycled by the compressor discharge pressure: it opens (loads) to build or maintain pressure, and closes (unloads) when rated pressure is achieved. When unloaded, the motor uses about 1/3 of the energy it uses while loaded.
  • While turning down energy use to 1/3 of full load is a great way to cut operating cost while maintaining operational integrity of your compressed air system, and physical integrity of your compressor, it doesn’t necessarily make sense when demand may be low enough to be serviced by existing system storage over long periods of time. That’s where Dual/Auto Dual control comes in. It allows you to select between Start/Stop and Load /Unload control modes.  Automatic Dual Control incorporates an over-run timer, so that the motor is stopped after a certain period of time without a demand. This method is most often used in facilities where different shifts have substantially different compressed air load requirements.

When any of the above control schemes are used, they will necessarily rely on having an adequate storage capacity…the compressor’s receiver, and intermediate storage (like EXAIR’s Model 9500-60 60 Gallon Receiver Tank, shown on right) must be adequately sized (and strategically located) to ensure adequate point-of-use pressures are maintained while the compressor’s motor or intake valve cycle. Other methods use variable controls to “tighten up” the cycle bands…these don’t rely on as much storage volume, and in some (but not all) cases, result in higher energy efficiency:

  • A variation of Load/Unload control, called Modulation, throttles the intake valve instead of opening & closing it, to maintain a specific system pressure. This method is limited in range from 100% to 40% of rated capacity, though, so it’s fairly inefficient in many cases.
  • Slide, spiral, or turn valves are built in to certain compressor designs to control output by a method called Variable Displacement, which (as advertised) changes the physical displacement volume of the air end. When header pressure rises, it sends a signal which repositions the valve progressively, reducing the working length of the rotors. This allows some bypass at the inlet, limiting the volume of air that’s being compressed with each turn of the rotor. Since the inlet pressure & compression ratio remain constant, the power draw from the partial load is considerably lower…so it costs less to operate. The normal operating range for this method is from 100% to 40% of rated capacity, but when used in conjunction with inlet valve Modulation, it’s effective & efficient down to 20% of rated capacity.
  • Of course, the most significant advance in efficient control of rotating industrial equipment since Nikola Tesla invented 3-phase AC is the Variable Speed Drive. When the frequency of the AC power supplied to an electric motor is changed, the speed at which it rotates changes in direct proportion. By applying this type of control to an air compressor, the motor’s speed is continuously controlled to match the air demand. Energy costs can be greatly reduced, as this method allows efficient turn down to as low as 20% of rated capacity.

As mentioned a couple times above, multiple control schemes can be applied, depending on user specific needs. Adding accessories, of course, adds cost to your capital purchase, but discussions with your air compressor dealer will lay out the pros, cons, and return on investment. While we don’t sell, service, or even recommend specific air compressors, EXAIR Corporation is in the business of helping you get the most out of your compressed air system. If you’d like to talk more about it, give me a call.

Russ Bowman, CCASS

Application Engineer
EXAIR Corporation
Visit us on the Web
Follow me on Twitter
Like us on Facebook

Compressed air Storage: Do you need a Receiver Tank?

Maintaining a “supply and demand” balance in the design & operation of compressed air systems often includes receiver tanks.

Just like in economics, we have to consider both sides – supply AND demand – to best maintain this balance.  Also like in economics, there are numerous factors…on both sides…but the two most critical factors are:

  • Compressor capacity control (supply side)
  • System storage (demand side)

I wrote a blog on “Air Compressor Motors and Controls, Working Together”, outlining the ‘supply side’ variables, today lets look at the system storage. Distribution piping makes up a certain amount of this, and another great blog from my colleague, Tyler Daniel – “Intelligent Compressed Air: Distribution Piping and Pressure Drop” – gets me off the hook for THAT part of the discussion today.

We can consider the air capacity of system piping to be fixed for the purposes of this discussion, so our “variable” will be the capacity of storage tanks. Let’s start with the reasons for the need for system storage: Strategically placed point-of-use air receivers provide stored energy for intermittent demands.  This enables the compressed air system to handle fluctuating loads, efficiently & reliably.  It also minimizes impact (e.g., sudden and often detrimental drops) on the system pressure.

Next, we’ll look at location. There are a couple of common options to consider:

  • The intermittent demand. Installing a receiver here will provide enough air for short duration, high consumption events, protecting the rest of the system from pressure excursions. Dedicating the receiver to this application will mean isolating it from the rest of the system with a check valve (so it only supplies the load in question) and a needle valve (so recharging the receiver itself, between the intermittent uses, doesn’t adversely affect total system pressure).
  • The critical load(s). Instead of using stored air for the intermittent load, you can also use it for the important loads you’re trying to protect. All sorts of machinery with pneumatic components can “crash” if a nearby intermittent demand starts up & “steals” their air. You’ll use a check valve (same as above), but using a needle valve to throttle the air flow that recharges the receiver risks “starving” the critical load. Don’t do that unless there’s a really good (and likely really specific) reason for it.

Finally, we’re going to do some math, so we know how big this receiver has to be. Here’s the equation we use to do that:

Let’s calculate the receiver size needed to supply an intermittent load of 400 SCFM (C) @80psig (P2), that’ll run for one minute (T). You can use data specific to your system to come up with a value for (Cap) but here I’m going to assume we want the receiver to be able to handle the whole thing, so Cap = 0. I’m also going to assume we’re at sea level, so Pa = 14.7psia and that our compressor’s discharge pressure (the pressure at which the receiver can be charged to) is 120psig (P1):

That’s an awfully big tank. Now, let’s calculate the receiver size needed to protect a critical load that uses 55 SCFM @60psig, and that due to the system design, we can count on 25 SCFM @120psig from the compressor:

This is a much more manageable size, in fact, our 60 Gallon Receiver Tank (Model 9500-60) would be ideal. It’s 20″ in diameter and just over 50″ tall, so it doesn’t take up a lot of floor space. It comes with a drain valve and connections for compressed air flow in & out, pressure gauge, relief valve, etc.

Step Five of our Six Steps To Optimizing Your Compressed Air System: Use intermediate storage near the point of use.

Now, the above example is a completely hypothetical situation, and I purposely chose exaggerated values to show that there can indeed be a clear “winner” in the choice between the two installation points. If you have a situation like this, and would like help in finding the solution that makes the most sense, give us a call.

Jordan Shouse
Application Engineer

Send me an Email
Find us on the Web 
Like us on Facebook
Twitter: @EXAIR_JS

How To Determine The Need For – And The Size Of – Compressed Air Receiver Tanks

Supply and Demand, in economics, defines the relationship between the volume of commodities that sellers want to exchange for a certain amount of currency, and the volume of said commodities that buyers are willing to exchange a certain (and sometimes different) amount of currency for.  The best chance for an ideal condition is when the volume produced is the same as the volume being consumed.  That typically means both sides are amenable to the same certain amount of currency, and everyone’s happy: the sellers are making a fair profit, and the buyers are paying a fair price.  Thing is, that’s a difficult balance to maintain.  The reasons for imbalances are often debated and usually contentious, and I have no intention of going in to them here.  I only brought up the subject to draw an analogy to the difficulties in maintaining a “supply and demand” balance in the design & operation of compressed air systems.

Just like in economics, we have to consider both sides – supply AND demand – to best maintain this balance.  Also like in economics, there are numerous factors…on both sides…but the two most critical factors are:

  • Compressor capacity control (supply side)
  • System storage (demand side)

My colleague Jordan Shouse wrote an excellent blog on “Air Compressor Motors and Controls, Working Together”, outlining the ‘supply side’ variables, allowing me to concentrate my efforts today on system storage. Distribution piping makes up a certain amount of this, and another great blog from another colleague, Tyler Daniel – “Intelligent Compressed Air: Distribution Piping and Pressure Drop” – gets me off the hook for THAT part of the discussion today.

We can consider the air capacity of system piping to be fixed for the purposes of this discussion, so our “variable” will be the capacity of storage tanks. Let’s start with the reasons for the need for system storage: Strategically placed point-of-use air receivers provide stored energy for intermittent demands.  This enables the compressed air system to handle fluctuating loads, efficiently & reliably.  It also minimizes impact (e.g., sudden and often detrimental drops) on the system pressure.

Next, we’ll look at location. There are a couple of common options to consider:

  • The intermittent demand. Installing a receiver here will provide enough air for short duration, high consumption events, protecting the rest of the system from pressure excursions. Dedicating the receiver to this application will mean isolating it from the rest of the system with a check valve (so it only supplies the load in question) and a needle valve (so recharging the receiver itself, between the intermittent uses, doesn’t adversely affect total system pressure).
  • The critical load(s). Instead of using stored air for the intermittent load, you can also use it for the important loads you’re trying to protect. All sorts of machinery with pneumatic components can “crash” if a nearby intermittent demand starts up & “steals” their air. You’ll use a check valve (same as above), but using a needle valve to throttle the air flow that recharges the receiver risks “starving” the critical load. Don’t do that unless there’s a really good (and likely really specific) reason for it.

Finally, we’re going to do some math, so we know how big this receiver has to be. Here’s the equation we use to do that:

Let’s calculate the receiver size needed to supply an intermittent load of 400 SCFM (C) @80psig (P2), that’ll run for one minute (T). You can use data specific to your system to come up with a value for (Cap) but here I’m going to assume we want the receiver to be able to handle the whole thing, so Cap = 0. I’m also going to assume we’re at sea level, so Pa = 14.7psia and that our compressor’s discharge pressure (the pressure at which the receiver can be charged to) is 120psig (P1):

That’s an awfully big tank. Now, let’s calculate the receiver size needed to protect a critical load that uses 55 SCFM @60psig, and that due to the system design, we can count on 25 SCFM @120psig from the compressor:

This is a much more manageable size, in fact, our 60 Gallon Receiver Tank (Model 9500-60) would be ideal. It’s 20″ in diameter and just over 50″ tall, so it doesn’t take up a lot of floor space. It comes with a drain valve and connections for compressed air flow in & out, pressure gauge, relief valve, etc.

Step Five of our Six Steps To Optimizing Your Compressed Air System: Use intermediate storage near the point of use.

Now, the above example is a completely hypothetical situation, and I purposely chose exaggerated values to show that there can indeed be a clear “winner” in the choice between the two installation points. “Your mileage may vary,” as the car folks say. If you have a situation like this, and would like help in finding the solution that makes the most sense, give me a call.

Russ Bowman, CCASS

Application Engineer
EXAIR Corporation
Visit us on the Web
Follow me on Twitter
Like us on Facebook

Cover image courtesy of: Tennessee Valley Authority; SVG version by Tomia, CC BY-SA 3.0 <http://creativecommons.org/licenses/by-sa/3.0/>, via Wikimedia Commons