Basics of the Compressed Air System

Compressed air is used to operate pneumatic systems within a facility, and it can be separated into three categories; the supply side, the demand side, and the distribution system.  In this blog, I will cover each area. 

The supply side is the air compressor, after-cooler, dryer, and receiver tank that produce and treat the compressed air.  They are generally located in a compressor room somewhere in the corner of the plant.  There are two main types of air compressors: positive displacement and dynamic.  The core component of most air compressors is an electric motor that spins a shaft.  Positive displacement uses the energy from the motor and the shaft to change volume in an area, like a piston in a reciprocating air compressor or like rotors in a rotary air compressor.  The dynamic types use the energy from the motor and the shaft to create a velocity with an impeller like centrifugal air compressors.  This velocity converts to a rise in pressure.

How do they work?  Most air compressors are driven by an electric or gas motor.  The motor spins a shaft to push a piston, turn a rotor, or spin a vane.  At the beginning of the air compressor, we have the intake where a low pressure is generated from the displacement to bring in the surrounding ambient air.  Once trapped, Boyle’s law states that when the volume decreases, the pressure increases.  For the dynamic type, the velocity and design will increase the air pressure.  The higher pressure will then move to a tank to be stored for pneumatic energy.  The amount of power required is dependent on the pressure and the amount of air that needs to be compressed. 

The demand side is the collection of devices that will use that compressed air to do “work”.  These pneumatic components are generally scattered throughout the facility.  This would include valves, cylinders, blow-offs, pneumatic clamps, etc.   To condition the demand side, regulators and filters are used.  The Pressure Regulators help to limit the amount of pressure.  For blow-off devices, the lower the air pressure to “do the job”, the less compressed air is used.  To help with the fluctuations in demand, a secondary Receiver Tank can be used.  The demand side can also be a system to do specific jobs. In using pneumatic systems, the “power” must come from the supply side. 

To connect the supply side to the demand side, a compressed air distribution system is required.  Distribution systems are pipes which carry the compressed air from the compressor to the pneumatic devices.  For a sound compressed air system, the three sections have to work together to make an effective and efficient system. An analogy that I like to use is to compare the compressed air system to an electrical system.  The air compressor would be considered the voltage source, and the pneumatic devices would be considered as light bulbs.  To connect the light bulbs to the voltage source, electrical wires are needed which will represent the distribution system.  If the gauge of the wire is too small to supply the light bulbs, the wire will heat up and a voltage drop will occur.  This heat is given off as wasted energy, and the light bulbs will be dim.  The same thing happens within a compressed air system.  If the piping size is too small, a pressure drop will occur.  This is also wasted energy.  In both types of systems, wasted energy is wasted money.  One of the largest systematic problems with compressed air systems is pressure drop.  With a properly designed distribution system, energy can be saved, and, in reference to my analogy above, it will keep the lights on.  To have a properly designed distribution system, the pressure drop should be less than 10% from the reservoir tank to the point-of-use.

Processes lead to continuous improvement.

EXAIR created the “Six Steps to Optimizing Your Compressed Air System”.  By following these tips, you can have the supply side, demand side, and distribution system working at peak efficiency.  If you would like to reduce waste even more, EXAIR offers a variety of efficient, safe, and effective compressed air products to fit within the demand side.  This will include the EXAIR Super Air Knives, Super Air Nozzles, and Safety Air Guns.  This would be the electrical equivalent of changing those incandescent light bulbs into LED light bulbs.  If you wish to go further in enhancing your system, an Application Engineer at EXAIR will be happy to help you. 

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Photo:  Lightbulb by qimono.  Pixabay Licence

Supply Side Review: Deliquescent Type Dryers

As mentioned in my post last week.  The supply side of compressed air systems within a facility is critical to production.  The quality of air produced by your compressor and sent to the demand side of the system needs to be filtered for both moisture and particulate.  One method to dry the air, that is the topic for this blog, is deliquescent type dryers.

These dryers operate like an adsorbent dryer such as a desiccant medium dryer.  The main variance is that the drying medium (desiccant) actually undergoes a phase change from solids to liquids.  Because of this the material is used up and cannot be returned to its original state for reuse.   The liquids formed by the desiccant dissolving in the removed water vapor are then filtered out of the air stream before it is passed on to the demand side of the air system.

There are many compounds that are used to absorb the moisture in the wet compressed air.  A few options are potassium, calcium, or sodium salts and many that contain a urea base.  The desiccant compound must be maintained at a minimum level for the dryer to contain enough media to successfully dry the air.

These dryers are generally a single tank system that is fed with compressed air from a side port near the bottom of the tank.  The air then travels up past drip trays where the desiccant and water mixture fall and ultimately ends up in the bottom of the tank.  The air then goes through a material bed that must be kept at a given level in order to correctly absorb the moisture in the air.  The dry air is then pushed out the top of the tank.

As the desiccant material absorbs the liquid from the compressed air flowing through the tank it falls onto the drip trays and then into the bottom of the tank where it is drained out of the system.  This process can be seen in the image below.

 

Deliquescent type compressed air drying system
How a deliquescent air dryer works – 1(VMAC Air Innovated, 2017)

 

The dew point that this style dryer is able to achieve is dependent on several variables:

  • Compressed air temperature
  • Compressed air pressure / velocity
  • Size and configuration of the tank
  • Compression of the absorption media
  • Type of absorption media and age of media

These dryers are simplistic in their design because there are no moving parts as well as easy to install and carry a low startup cost.

Some disadvantages include:

  • Dewpoint range 20°F – 30°F (Again this is according to the media used.)
  • Dissolved absorption material can pose a disposal issue as it may not be able to be simply put down a drain
  • Replacement of the absorption material

Even with disadvantages the ability to supply the demand side of a compressed air system for a production facility is key to maintaining successful operations.  If you would like to discuss any type of compressed air dryer, please contact us.

Brian Farno
Application Engineer
BrianFarno@EXAIR.com
@EXAIR_BF

 

1 – Deliquescent Dryer Image: VMAC Air Innovated: The Deliquescent Dryer – https://www.vmacair.com/blog/the-deliquescent-dryer/