Refrigerant Compressed Air Dryer Systems

No matter what your use of compressed air entails, moisture is very likely an issue.  Air compressors pressurize air that they pull in straight from the environment and most of the time, there’s at least a little humidity involved.  Now, if you have an industrial air compressor, it’s also very likely that it was supplied with a dryer, for this very reason.

There are different types of dryer systems, depending on your requirements.

For practical purposes, “dryness” of compressed air is really its dew point.  That’s the temperature at which water vapor in the air will condense into liquid water…which is when it becomes the aforementioned issue in your compressed air applications.  This can cause rust in air cylinders, motors, tools, etc.  It can be detrimental to blow offs – anything in your compressed air flow is going to get on the surface of whatever you’re blowing onto.  It can lead to freezing in Vortex Tube applications when a low enough cold air temperature is produced.

Some very stringent applications (food & pharma folks, I’m looking at you) call for VERY low dew points…ISO 8673.1 (food and pharma folks, you know what I’m talking about) calls for a dew point of -40°F (-40°C) as well as very fine particulate filtration specs.  As a consumer who likes high levels of sanitary practice for the foods and medicines I put in my body, I’m EXTREMELY appreciative of this.  The dryer systems that are capable of low dew points like this operate as physical filtration (membrane types) or effect a chemical reaction to absorb or adsorb water (desiccant or deliquescent types.)  These are all on the higher ends of purchase price, operating costs, and maintenance levels.

For many industrial and commercial applications, though, you really just need a dew point that’s below the lowest expected ambient temperature in which you’ll be operating your compressed air products & devices.  Refrigerant type air dryers are ideal for this.  They tend to be on the less expensive side for purchase, operating, and maintenance costs.  They typically produce air with a dew point of 35-40°F (~2-5°C) but if that’s all you need, they let you avoid the expense of the ones that produce those much lower dew points.  Here’s how they work:

  • Red-to-orange arrows: hot air straight from the compressor gets cooled by some really cold air (more on that in a moment.)
  • Orange-to-blue arrows: the air is now cooled further by refrigerant…this causes a good amount of the water vapor in it to condense, where it leaves the system through the trap & drain (black arrow.)
  • Blue-to-purple arrows: Remember when the hot air straight from the compressor got cooled by really cold air? This is it. Now it flows into the compressed air header, with a sufficiently low dew point, for use in the plant.

Non-cycling refrigerant dryers are good for systems that operate with a continuous air demand.  They have minimal dew point swings, but, because they run all the time, they’re not always ideal when your compressed air is not in continuous use.  For those situations, cycling refrigerant dryers will conserve energy…also called mass thermal dryers, they use the refrigerant to cool a solution (usually glycol) to cool the incoming air.  Once the glycol reaches a certain temperature, the system turns on and runs until the solution (thermal mass) is cooled, then it turns off.  Because of this, a cycling system’s operating time (and cost) closely follows the compressor’s load – so if your compressor runs 70% of the time, a cycling dryer will cost 30% less to operate than a non-cycling one.

EXAIR Corporation wants you to get the most out of your compressed air system.  If you have questions, I’d love to hear from you.

Russ Bowman
Application Engineer
EXAIR Corporation
Visit us on the Web
Follow me on Twitter
Like us on Facebook

Compressed Air and Dew Point

Today’s discussion is on dew point of air as it has a significant impact on a compressed air system. The dew point is the temperature at which the water vapor in the air  can no longer stay in a vapor form, and condenses from a vapor into a liquid. The amount of water vapor contained in air is directly proportional to its temperature. The warmer the air the more space there is between molecules thus it is able to hold more water vapor.Capture

It is when air temperature drops below the dew point that issues develop in a compressed air system. Let’s take the example of a warm summer day at 90 F and 50% relative humidity. From the chart we see the dew point temperature to be 70 F. So at night, when all the equipment is shut down and the temperatures drop into the 60’s, water will condensate throughout the entire system. In the morning when the equipment is turned on, water blows through sensitive valving.

Compressing air will increase the dew point. Hot compressed air exiting the compressor and cooling while it makes its way through distribution systems is one reason for condensate in compressed air lines. Drying the compressed air is recommended to reduce or eliminate water condensate problems in a compressed air system.

There are several methods to dry out your compressed air. Each have their advantages and disadvantages. The following short review of the various options will help you decide which is best for your application.

After-coolers

The compressor’s after-cooler  which looks similar to a car’s radiator or the condenser in an air conditioner, is the first step to dryer air. It is placed at the compressor’s air outlet and uses either ambient air or water to cool the compressed air and condense some of the water vapor into a liquid that can be removed with a water separator.

The simplicity of design is a positive. The negative is that it can never cool below ambient but something above ambient depending on its capacity. After-cooler performance is rated by approach temperature, which is how closely the compressed air leaving the after-cooler will approach the temperature of the cooling medium used.

For example, if an air-cooled after-cooler is rated for a 10°F approach temperature, and the temperature of the ambient air is 90°F, the temperature of the air leaving the after-cooler will be 100°F. Assuming 50% relative humidity day the dew point will be 80 F.

Mechanical Water Separators

????????????????????????????????????????

Wet compressed air enters the separator and passes through a set of vanes that spins it in a vortex. Centrifugal force causes liquid to fly out of the compressed air stream and run down the inside of the filter bowl, where it can be drained off. These are installed at the point of use as a final defense before entering sensitive compressed air equipment. They are an inexpensive assurance of quality air. The ones EXAIR has also include a sintered bronze filter element to remove dirt and scale as well as water.

Deliquescent Dryer

A deliquescent dryer is basically a tank full of salt tablets. As the compressed air passes through the salt, the salt attracts water and dissolves into a brine that can be drained off. These are the least expensive dryers to purchase and maintain because they have no moving parts and require no power to run. The operating cost consists of the cost of more salt tablets.

Desiccant Air Dryers

These are similar to the deliquescent driers except they use a desiccant that attracts water but holds it. When they have reached their saturation limit they are either replaced or regenerated in one of three methods.

Operating cost of these dryers varies with the method used to remove water from or regenerate the desiccant.

Heatless regenerative dryers take a portion (about 15%) of the dry compressed air leaving the dryer and passes it through the desiccant to absorb the moisture out of it. Purchase cost economical but operational costs are high because if all the compressed air used to dry out the desiccant.

Heated purge regenerative dryers take advantage of the fact that hot air can hold more water than cold air. These dryers take about 5% of the dry compressed air leaving the dryer and pass it through an electric heater and then sends it through the wet desiccant bed. This dryer cost more than the heat less dryer but is offset by using half the compressed of that used by the heat less dryer.

Blower Purge Dryers

These are similar in concept to the had dryers found in restrooms but on a larger scale. Heated air is sent trough the desiccant with a blower. These are not quite as efficient because they are heating up ambient air which would not be as dry as compressed air.

Membrane Air Dryers

These dryers use pass the compressed air through a membrane with pores large enough to allow air molecules through but not large enough to allow water molecules through. The lower a dew point is needed, the more purge air is required. These

Refrigerated Air Dryers

Is an A/C system that refrigerate  the compressed air as close to freezing as possible in order to condense out as much water as possible then use a mechanical water separators to remove the condensed water. They require electricity to operate along with the associated cost of operation and maintenance.

Hopefully this gives you a better understanding on how to qualify your compressed air.