The Effect of Back Pressure on a Vortex Tube Part 2, Calculating Btu/Hr.

My previous blog post was about how Vortex Tubes react when there is back pressure due to a restriction on either the hot or cold discharge of the Vortex Tube.  In it I mentioned that there is a formula to calculate what the cooling capacity (Btu/Hr) will be if there is no way to avoid operating the Vortex Tube without back pressure on the discharge. That is the calculation focus of this blog – calculating Btu/hr of a Vortex Tube with back pressure.

To continue with the same example, the calculations from the previous blog are shown below.  Last time the example Vortex Tube was operating at 100 psig inlet pressure, 50% cold fraction, and 10 psi of back pressure. We will need some additional information to determine the Btu/Hr capacity. The additional information needed is the temperature of the supplied compressed air as well as the ambient air temperature desired to maintain.  For the example the inlet compressed air will be 70°F and desired ambient air temperature to maintain will be 90°F.

(100 psig + 14.7 psia) / (10 psig + 14.7 psia) = X / 14.7 psia
4.6437 = X / 14.7
X= 14.7 * 4.6437
X = 68.2628
(Values have been rounded for display purposes)

The calculation above gives the compensated operating pressure (X = 68.2628) which will be needed for the BTU/hr calculation. The rated air consumption value of the Vortex Tube will also need to be known.  A 30 SCFM rated generator will be used for this example, the normal BTU capacity of a Vortex Tube with a 30 SCFM generator is 2,000 BTU/hr.

First, determine the new consumption rate by establishing a ratio of the compensated pressure (68.2628 psi) against the rated pressure (100 psi) at absolute conditions (14.7 psia).

(68.2628 PSIG + 14.7 (atmospheric pressure)) / (100 PSIG (rated pressure) + 14.7) = .7233
.7233 x 30 SCFM  = 21.7 SCFM Input 

Second, the volumetric flow of cold air at the previously mentioned cold fraction (50%) will be calculated.  To do this multiply the cold fraction setting (50%) of the Vortex Tube by the compensated input consumption (21.7 SCFM) of the Vortex Tube.

50% cold fraction x 21.7 SCFM input = 10.85 SCFM of cold air flow

Third, the temperature of air that will be produced by the Vortex Tube will need to be calculated.  For this consult the Vortex Tube performance chart which is shown below. To simplify the example the compensated operating pressure (68.2628 psi) will be rounded to 70 psig and to obtain the 70 psig value the mean between 80 psig and 60 psig performance from the chart will be used.

Cold Fraction
EXAIR Vortex Tube Performance Chart

For the example: A 70 psig inlet pressure at 50% cold fraction will produce approximately an 88°F drop.
Fourth, subtract the temperature drop (88°F) from the temperature of the supplied compressed air temperature (70°F).

70°F Supply air – 88°F drop = -18°F Output Air Temperature

Fifth,  determine the difference between the temperature of the air being produced by the Vortex Tube (-18°F) and the ambient air temperature that is desired (90°F).

90°F ambient – -18°F air generated = 108°F difference.

The sixth and final step in the calculation is to apply the answers obtained above into a refrigeration formula to calculate BTU/hr.

1.0746 (BTU/hr. constant for air) x 10.85 SCFM of cold air flow x 108°F ΔT = 1,259 BTU/hr.

In summary, if a 2,000 BTU/hr. Vortex tube is operated at 100 psig inlet pressure, 50% cold fraction, 70°F inlet air to maintain a 90°F ambient condition with 10 psi of back pressure on the outlets of the Vortex Tube the cooling capacity will be de-rated to 1,259 BTU/hr.  That is a 37% reduction in performance.  If a back pressure cannot be avoided and the cooling capacity needed is known then it is possible to compensate and ensure the cooling capacity can still be achieved.  The ideal scenario for a Vortex Tube to remain at optimal performance is to operate with no back pressure on the cold or hot outlet.

Brian Farno
Application Engineer Manager
BrianFarno@EXAIR.com
@EXAIR_BF

The Effect of Back Pressure on a Vortex Tube

Vortex tubes have been considered a phenomena of Physics and boggled minds for many years.  To give a brief run down of how the Vortex Tube works please refer to Figure 1 below.

How_A_Vortex_Tube_Works
Figure 1

As seen above, the control valve is determining the amount of air allowed to escape the hot end and sets the cold fraction.  A cold fraction is the percentage of air that exits the cold side versus the hot side. The cold fraction and operating pressure sets the temperature drop on the cold end and temperature rise on the hot end, as well as volumetric flow out of both ends. The control valve is not the only variable that can alter the cold fraction of the Vortex Tube though.

In Figure 1 and the performance chart below, there is no restriction on the hot end or the cold end outlets. No restriction means no back pressure and the cold air has the easiest path to the area needing cooling. Back pressure can directly affect the performance of a Vortex Tube.  As little as 3 psig of back pressure can begin to alter the temperature drop or rise on the Vortex Tube.  This is due to the fact that Vortex Tubes operate off an absolute pressure differential.  If the outlets have a restriction on them then they are not discharging at atmospheric pressure, 14.7 psi. What kind of items can cause back pressure and can the performance with a back pressure on the outlet be determined?

Back pressure is created by implementing any form of restriction on the hot or cold outlet. This may be undersized tubing to deliver the cold air or a valve that has been installed to try and control the volume of air being blown onto the process as well as many other possibilities.  The best rule of thumb to eliminate back pressure is to keep the tubing on an outlet the same cross sectional dimension as the outlet on the Vortex Tube and try to keep the tubing as short as possible.

If back pressure cannot be prevented, the performance variance of the Vortex Tube can be calculated and possibly compensated for. The variables that are needed to do so are the inlet air pressure of the vortex tube and the amount of back pressure that is being seen on the outlets. If this is different from the hot end to the cold end both will need to be known.  If these are not known they can be measure by installing a pipe Tee and a pressure gauge. This may need to be a sensitive pressure gauge that measures even relatively low psig. (1-15 psig)

Once these variables are known, we want to look at an absolute pressure differential versus the back pressure differential. For example, the Vortex Tube is a operating at 100 psig inlet pressure, 50% cold fraction and 10 psi of back pressure.  We look at the pressure differentials and can use Algebraic method to determine the inlet pressure supply that the tube will actually perform at.

(100 psig + 14.7 psia) / (10 psig + 14.7 psia) = X / 14.7 psia
4.6437 = X / 14.7
X= 14.7 * 4.6437
X = 68.2628
(Values have been rounded for display purposes)

So if there is a 10 psig back pressure on the outlet of a Vortex tube operating a 100 psig inlet pressure the tube will actually carry performance as if the inlet pressure was ~68 psig.   To showcase the alteration in performance we will look at just the temperature drop out of the cold side of the Vortex Tube. (Keep in mind this is a drop from the incoming compressed air temperature.)

Vortex Tube Performance Data
Vortex Tube Performance Chart

As shown in the performance chart above, if the Vortex Tube was operating at 100 psig inlet pressure and 50% cold fraction the temperature drop would be 100°F.  By applying a 10 psi back pressure on the outlet of the Vortex Tube the temperature will be decreased to ~87°F temperature drop.   This will also decrease the volumetric flow of air exiting the Vortex Tube which can also be calculated in order to determine the cooling capacity of the Vortex Tube at the altered state.  Keep an eye out for a follow up blog coming soon to see that calculation.

Brian Farno
Application Engineer Manager
BrianFarno@EXAIR.com
@EXAIR_BF

Compressed Air – Diagnose a Car Problem or Simulate Ape Breath

At the end of this week and all through next week, I will be taking my family to the “most magical place on earth!”  Keep in mind, I have three daughters at the ages of 5 (almost 6 if you ask her), 3, and 1. (Not to mention my wife who has spent endless hours researching and scheduling our events for the week.) It’s not just my household that is going on this trip though, it is my entire family, parents, siblings, teenage nieces, and one nephew.   I honestly don’t remember the last family vacation we went on with all of us there so it is going to be an amazing experience no matter what.

Cin-Orl
Cincinnati to Orlando = 13 hours (not with kids)

The trip from Cincinnati, OH to Orlando, FL is approximately 13 hours, factor in the children and parents ages and I am going to go ahead and say we are looking at 24 hours of travel, at least.   Now I am being smart, we are breaking this trip up into two days. I envision something that will look like a military convoy going down I-75 when the 3 vehicles all get going, the painful truth is it will look more like the Clampets move to Hollywood.

In preparation for the trip I have been doing some routine maintenance on our family van and discovered what I believed to be a rather bad coolant leak.  Now, I didn’t see the leak but I noticed the lack of coolant in the system.   So I started to conduct a few tests and oddly enough, they involved compressed air.   First I filled the system and pulled a vacuum on the entire cooling system to draw out any air.   Once I pulled around 11″ of mercury, I went ahead and turned off my compressed air vacuum generator and tried to see if it would lose vacuum.  It didn’t, so I then hooked a hose to a container of coolant and slowly released the vacuum sucking the coolant down into the system and eliminating the risk of air bubbles.

Since I couldn’t see a loss in vacuum I decided I would test the system under pressure.  To do this I simply removed the radiator cap and attached a special tool which would pump air down into the radiator and put the entire system under pressure, much like it would be during normal operation.  Once I built the pressure up to 15 psig, the factory cap was rated for 16 psig,  I let it sit.  I scoured every single coolant line I could find and came up dry.  Couldn’t find a single drop of coolant escaping the system at all and it even held pressure for a solid hour. Coming up with no leak I decided to give it a test drive and low and behold, I have yet to find a leak.  My only theory at this point is during some warranty work a dealership must have disconnected a hose and forgot to fill it back up, or it is normal evaporation seeing as how I don’t remember the last time I topped off the coolant.

The entire time I was troubleshooting this system I found it interesting I was still using compressed air in some form, even on a liquid cooling system.  I then started to wonder if I am going to be able to see any EXAIR products while at that magical park in Orlando, hopefully something like the Roaring Banana Breath that is featured in our Super Air Amplifiers section of the catalog. Our amplifiers also get used to puff air at folks during other “4D” experiences throughout the world.

banana
EXAIR Super Air Amplifiers help disperse banana scents into the air and into the face of patrons at a theme park ride.

Nonetheless, compressed air helped me determine that my family’s vehicle is not going to be spraying coolant on the roadway during this trip and I am glad for it.

Brian Farno
Application Engineer Manager
BrianFarno@EXAIR.com
@EXAIR_BF

 

Back Blow Nozzles: When Blowing Forward Is Not An Option

Have you ever been in a situation where you need to blow debris or chips out of a pipe or a blind hole?   Maybe it is a pipe you are saw cutting and don’t want to push chips and debris further down the pipe line  You could be trying to clean out a pipe that has debris inside and and can’t push it further down the line because it could damage other system components.  Other customers cleaning out inside diameters of pipe cannot blow all the way out the other side of the pipe due to people being present on that end of the pipe and need to avoid harming them.

The Model 1006SS cleans metal shavings from inside a pipe.
The Model 1006SS cleans metal shavings from inside a pipe.

This is where EXAIR has seen an opening in our product offering and we have filled the void yet again.  We currently offer two sizes of the EXAIR Back Blow Nozzle.   The 1/4″ NPT version, model 1006SS is made to clean out pipes from 7/8″ I.D. to 4″ I.D.   The 1″ NPT version, model 1008SS, is best suited for pipes from 2″ I.D. to 16″ I.D.

Various Views of the Model 1006SS Back Blow Nozzle
Various Views of the Model 1006SS Back Blow Nozzle

 

Airflow Patterns for EXAIR Back Blow Nozzles
Airflow Patterns for EXAIR Back Blow Nozzles

 

So if you have a critical operation or even just a saw cut and don’t want to blow debris further down the pipe, tube or extrusion, contact us about the EXAIR Back Blow Nozzle.

Brian Farno
BrianFarno@EXAIR.com
@EXAIR_BF