The Effect of Back Pressure on a Vortex Tube

Vortex tubes have been considered a phenomena of Physics and boggled minds for many years.  To give a brief run down of how the Vortex Tube works please refer to Figure 1 below.

How_A_Vortex_Tube_Works
Figure 1

As seen above, the control valve is determining the amount of air allowed to escape the hot end and sets the cold fraction.  A cold fraction is the percentage of air that exits the cold side versus the hot side. The cold fraction and operating pressure sets the temperature drop on the cold end and temperature rise on the hot end, as well as volumetric flow out of both ends. The control valve is not the only variable that can alter the cold fraction of the Vortex Tube though.

In Figure 1 and the performance chart below, there is no restriction on the hot end or the cold end outlets. No restriction means no back pressure and the cold air has the easiest path to the area needing cooling. Back pressure can directly affect the performance of a Vortex Tube.  As little as 3 psig of back pressure can begin to alter the temperature drop or rise on the Vortex Tube.  This is due to the fact that Vortex Tubes operate off an absolute pressure differential.  If the outlets have a restriction on them then they are not discharging at atmospheric pressure, 14.7 psi. What kind of items can cause back pressure and can the performance with a back pressure on the outlet be determined?

Back pressure is created by implementing any form of restriction on the hot or cold outlet. This may be undersized tubing to deliver the cold air or a valve that has been installed to try and control the volume of air being blown onto the process as well as many other possibilities.  The best rule of thumb to eliminate back pressure is to keep the tubing on an outlet the same cross sectional dimension as the outlet on the Vortex Tube and try to keep the tubing as short as possible.

If back pressure cannot be prevented, the performance variance of the Vortex Tube can be calculated and possibly compensated for. The variables that are needed to do so are the inlet air pressure of the vortex tube and the amount of back pressure that is being seen on the outlets. If this is different from the hot end to the cold end both will need to be known.  If these are not known they can be measure by installing a pipe Tee and a pressure gauge. This may need to be a sensitive pressure gauge that measures even relatively low psig. (1-15 psig)

Once these variables are known, we want to look at an absolute pressure differential versus the back pressure differential. For example, the Vortex Tube is a operating at 100 psig inlet pressure, 50% cold fraction and 10 psi of back pressure.  We look at the pressure differentials and can use Algebraic method to determine the inlet pressure supply that the tube will actually perform at.

(100 psig + 14.7 psia) / (10 psig + 14.7 psia) = X / 14.7 psia
4.6437 = X / 14.7
X= 14.7 * 4.6437
X = 68.2628
(Values have been rounded for display purposes)

So if there is a 10 psig back pressure on the outlet of a Vortex tube operating a 100 psig inlet pressure the tube will actually carry performance as if the inlet pressure was ~68 psig.   To showcase the alteration in performance we will look at just the temperature drop out of the cold side of the Vortex Tube. (Keep in mind this is a drop from the incoming compressed air temperature.)

Vortex Tube Performance Data
Vortex Tube Performance Chart

As shown in the performance chart above, if the Vortex Tube was operating at 100 psig inlet pressure and 50% cold fraction the temperature drop would be 100°F.  By applying a 10 psi back pressure on the outlet of the Vortex Tube the temperature will be decreased to ~87°F temperature drop.   This will also decrease the volumetric flow of air exiting the Vortex Tube which can also be calculated in order to determine the cooling capacity of the Vortex Tube at the altered state.  Keep an eye out for a follow up blog coming soon to see that calculation.

Brian Farno
Application Engineer Manager
BrianFarno@EXAIR.com
@EXAIR_BF

An Ultrasonic Leak Detector Helps a Fire Marshal With a Dry Sprinkler System

A dry sprinkler system? How will that help in a fire? The fire marshal snickered as he told me that this type of system was designed for cold weather fire protection.  Most sprinkler systems that we see in the ceiling are designed with water in the lines.  But, if you have areas that get below 40 deg. F (4 deg. C), the fire department will have you install a dry sprinkler system.  It uses compressed air to hold a valve shut to not allow the water to be inside the cold pipes. So, if you have an unheated crawl space, uninsulated attics, or an outside storage facility, you won’t have to worry about the water freezing and bursting your pipes or sprinkler heads.

The reason that the fire marshal contacted me was to help find a leak in a dry sprinkler system. A facility in his jurisdiction noticed that the air compressor that was assigned to the dry sprinkling system was cycling more often.  This was an indication of a leak, and just like any compressed air system, leaks occur over time at the connection points.  This facility had their pipes located in a crawl space, and there wasn’t much room for maneuvering.  Typically the normal protocol for a leak would be to go to each joint and spray it with soapy water.  If they saw bubbles, then they would fix that connection.  With the small space and the number of connections, he had to find a better way.

Model 9061

Whenever a leak occurs, it will generate an ultrasonic noise. The model 9061 Ultrasonic Leak Detector can pick up these high frequencies in the range of 20 Khz to 100 Khz, above human hearing.  This device makes the inaudible leaks, audible.  With three sensitivity ranges and LED display, you can find very small leaks, and with the two attachments, it can locate them up to 20 feet (6.1 meters) away.  When he started using it, he was amazed with the performance.  The Ultrasonic Leak Detector cut his time in the field and ensured that all the leaks were found.  In this instance, he was able to use the parabola attachment to locate the area of the leak from a distance.  He then crawled to that area and used the tube attachment to locate the exact location.  He found the leak and had it fixed.  If he did not have the Ultrasonic Leak Detector, he would have to maneuver his way throughout the small crawl space and spray soapy water on each fitting.

If you ever get stuck with a huge task with your compressed air system, like our fire marshal above, you can contact an Application Engineer at EXAIR to see if we can improve your situation.

John Ball
Application Engineer
Email: johnball@exair.com
Twitter: @EXAIR_jb

Overheating Problems in the Dead of Winter

Internal components of electro-pneumatic panel
Components housed in this customer’s electrical panel

Sometimes it can be easy to see enclosure overheating as strictly a seasonal problem related to outside temperatures.  And, while high ambient temperatures will certainly have an effect on the heat load within an electrical panel, overheating conditions can still occur inside a cabinet, even when there is ice outside.

Case in point, I received an email today from an end user I worked with last summer.  At the time, they were experiencing a seasonal overheating condition and needed a reliable method to remove the heat from their electrical panels.  We went through the Cabinet Cooler sizing process, determined the proper fit for their high temperature application, and found a suitable solution.

Fast-forward to today, and they have a new application with a similar condition.  The new application houses nearly identical components, but inside of a larger panel.  The larger surface area of the larger panel transfers more heat from the ambient space to the internals of the electrical panel.  This means that the total heat load of the application can and, most likely, will increase.

So, we recalculated the heat load for the larger enclosure size, and sure enough, a larger Cabinet Cooler was needed.  Again taking into account the high temperature characteristics of the application, we were able to determine the proper Cabinet Cooler to remove the unwanted heat.

It was nice to see a returning customer remembering the value of an EXAIR solution.  If you’re in a similar position, or if you’re simply interested in what an EXAIR product could do for your application, contact an EXAIR Application Engineer.

Lee Evans
Application Engineer
LeeEvans@EXAIR.com
@EXAIR_LE

Line Vacs Save Time And Backs

I had the pleasure of working with a customer at a chemical processing plant recently who happened upon our Line Vac Air Operated Conveyors while searching for something to move powdered chemical compounds. They receive these in powdered or granular forms, in 15-20 gallon containers that weigh 180-190 pounds each. These were being lifted and dumped, by hand, into the processing mixer. During a recent safety audit, they noticed a number of employees had missed work due to back injuries & pain. This prompted them to look for an alternative to the manual lifting of the drums.

They found auger conveyors and elaborate vacuum transfer systems, but when they saw our Line Vac Video…

…it was EXACTLY what they had in mind. The quick and easy setup was a big plus too – “Are you sure that’s all it takes?” was asked several times during our original conversation. Once the first Model 150200 2″ Heavy Duty Line Vac was received and set up – in about an hour from opening the box, by the way – they were pleased enough to call me back and tell me I was right (of course I was) and that the Heavy Duty Line Vac actually exceeded their expectations for both ease of setup and simplicity of operation. And, obviously, everyone’s going to be happier, now that the cumbersome, heavy lifting of the drums has been eliminated.

If you’re lifting containers of bulk material, whether your back hurts (yet) or not, give us call. We’ve got something for that.

Russ Bowman
Application Engineer
Find us on the Web
Follow me on Twitter
Like us on Facebook