Hazardous Location Cabinet Cooler Systems “Make Things Better”

In a previous arc in my career path, I worked on, and then built, and then sold industrial pumps, so I’ve been in my fair share of chemical plants. Did you ever wonder what all these places make? A decent number of them make what are called “intermediates”. These are compounds, solutions, & substances that aren’t found in stores, but go into almost all of the goods that ARE found in stores. One such company used to make commercials that explained it nicely:

I recently had the pleasure of assisting a caller from a company like this, who wanted to install three of our Hazardous Location Cabinet Cooler Systems in their facility. This particular company doesn’t make anything shown in the commercial above; they make intermediates for agricultural use (to paraphrase the commercial, “they don’t make fertilizer; they make fertilizer better”). As is the case in MANY chemical plants, a good portion of their real estate is classified as hazardous area (as defined by regulatory oversight agencies) AND subject to exposure to some fairly corrosive chemicals. Now, these places all go to great lengths to ensure safety for personnel AND equipment, through compliance AND design. So, when they needed to add durable & reliable heat protection to their electrical panels, they called EXAIR.

This was a pretty easy application, as the engineer I spoke to had gotten the internal heat loads from the equipment supplier, and already knew that 316SS construction was needed for the corrosive elements the equipment could be exposed to. The panel was in a Class I Div 2 area (flammable gasses or vapors may be present in the event of an accident or during unusual operating conditions). After calculating the external heat load, we specified a Model HZ4725SS-316 NEMA 4X (316SS Construction) Hazardous Location Cabinet Cooler System, rated for 1,700 Btu/hr, and Model 902021 24VDC HazLoc Solenoid Valve. These panels came equipped with temperature monitors that they could wire our valves into, otherwise we’d have supplied Thermostat Controlled systems.

EXAIR HazLoc Cabinet Cooler Systems are rated for Class I Div 1 & 2, Class II Div 1 & 2, and Class III environments.

EXAIR Cabinet Cooler Systems are available, from stock, to suit most any electric/electronic panel heat protection need:

  • Cooling capacities from 275 to 5,600 Btu/hr. Call me if your heat load is outside this range…we can look at customized solutions too.
  • NEMA 12 (IP54), 4, or 4X (IP66) ratings.
  • Thermostat Control – Standard, or Electronic Temperature Control.
  • Non-Hazardous Purge for contaminant exclusion on less-than-ideally sealed enclosures.
  • High Temperature models for ambient temperatures from 125°F (52°C) to 200°F (93°C).
  • Side Mount Kits when space is limited above the panel.
  • 316SS construction for particularly aggressive environments.
  • UL Classified for hazardous locations, just like the one I wrote about above.

If you’d like to find out how easy it is to provide durable and reliable heat protection for your electrical panels, give me a call.

Russ Bowman, CCASS

Application Engineer
EXAIR Corporation
Visit us on the Web
Follow me on Twitter
Like us on Facebook

Cabinet Cooling with Thermostat Control and ETC

An EXAIR Cabinet Cooler® System with either the Thermostat Control or the Electronic Temperature Control (ETC) option includes a temperature measuring device that is used to control the operation of the Cabinet Cooler System to maintain the set-point temperature.Thermostat and ETC

For most industrial enclosure cooling applications, a temperature of 95°F (35°C) is sufficient to be below the rated maximum operating temperature of the electrical components inside the cabinet. EXAIR Thermostats are preset to 95°F (35°C) and are adjustable. Maintaining the cabinet at 95°F (35°C) will keep the electronics cool and provide long life and reduced failures due to excessive heat. But if 95°F (35°C) is good, why not cool the cabinet to 70°F (21.1°C)?

When cooling an enclosure to a lower temperature, two things come into play that need to be considered. First, the amount of external heat load (the heat load caused by the environment) is increased. Using the table below, we can see the effect of cooling a cabinet to the lower temperature. For a 48″ x 36″ x 18″ cabinet, the surface area is 45 ft² (4.18 m²). If the ambient temperature is 105°F (40.55°C), we can find from the table the factors of 3.3 BTU/hr/ft² and 13.8 BTU/hr/ft² for the Temperature Differentials of 10°F (5.55°C) and 35°F (19.45°C). The factor is multiplied by the cabinet surface area to get the external heat load. The heat load values calculate to be 148.5 BTU/hr and 621 BTU/hr, a difference of 472.5 BTU/hr (119.1 kcal/hr)

External Heat Load

The extra external heat load of 472.5 BTU/hr (119.1 kcal/hr) will require the Cabinet Cooler System to run more often and for a longer duration to effectively remove the additional heat. This will increase, unnecessarily, the operating costs of the cooling operation.

The other factor that must be considered when cooling an enclosure to a lower temperature is that the Cabinet Cooler cooling capacity rating is effected. I won’t go into the detail in this blog, but note that a 1,000 BTU/hr Cabinet Cooler (rated for 95°F (35°C cooling) working to cool a cabinet down to 70°F (21.1°C) instead of 95°, has a reduced cooling capacity of 695 BTU/hr (174 kcal/hr).  The reduction is due to the cold air being able to absorb less heat as the air rises in temperature to 70°F instead of 95°F.

In summary – operating a Cabinet Cooler System at 95°F (35°C) provides a level cooling that will keep sensitive electronics cool and trouble-free, while using the least amount of compressed air possible.  Cooling to below this level will result in higher operation costs.

If you have questions about Cabinet Cooler Systems or any of the 15 different EXAIR Intelligent Compressed Air® Product lines, feel free to contact EXAIR and myself or any of our Application Engineers can help you determine the best solution.

Brian Bergmann
Application Engineer
Send me an email
Find us on the Web 
Like us on Facebook
Twitter: @EXAIR_BB

EXAIR’s Electronic Temperature Control for Cabinet Coolers

48xx-ETC120
EXAIR NEMA 4X 316SS Cabinet Cooler System with Electronic Temperature Control installed on control panel in a pharmaceutical plant.

Are you concerned about high temperatures this summer causing problems on your control panels? EXAIR’s Electronic Temperature Control (ETC) can be used with an EXAIR Cabinet Cooler to maintain precise control of the temperature inside of the cabinet. The ETC is available in both 110 and 240 VAC and is compatible with all Cabinet Cooler Systems.

After taking a few quick measurements, fill out the Cabinet Cooler Sizing Guide and an Application Engineer will be in touch with you to provide the most suitable system for your conditions. Don’t wait until the heat becomes a major problem, get yourself a Cabinet Cooler installed today and stop worrying about those high ambient temperatures!!

Tyler Daniel
Application Engineer
E-mail: TylerDaniel@exair.com
Twitter: @EXAIR_TD

 

Cabinet Cooler Systems – Around The Clock (And Calendar) Heat Protection

So it was 19°F (-7°C) when I walked outside this morning. The layer of ice on my windshield was thin, but particularly stubborn, and I muttered under my breath. I have no business complaining about the cold…see, I moved to Ohio (on purpose) from Florida, in 1991. In November, to be exact. I still remember where I surrendered my “complain-about-the-cold” card:

If you’re headed north on I95, the next sign you’ll see is in Georgia. And if you’re not careful, you can end up “Up North.”

Why am I writing a blog about solutions to heat problems when, even though I do have a really nice pair of gloves, my fingers still aren’t even really thawed from ice removal duty this morning? Well, I’ve got three reasons:

1. Outside temperature doesn’t necessarily have any bearing at all on the temperature inside. Sure; there’s a reason we call July and August “Cabinet Cooler Season” – summer heat will do a number on sensitive electronic & control panels in spaces with no climate controls, but the problem goes away as winter approaches. In fact, there’s even such as thing as a cabinet HEATER, if the equipment in question is exposed to the elements.   Sometimes, though, heat is an issue year ’round…think blast furnaces, boiler rooms, foundries, chemical plants.  If your process generates heat, it’ll affect a control panel in the dead of winter just the same as on the dog days of summer.  We can quickly and easily specify the right Cabinet Cooler System for you with just a few key pieces of data…here’s a link to our Cabinet Cooler Sizing Guide if you want to find out.

2. It’s not winter all over the world.  Here in the Midwest United States, I full well realize we’re just gearing up for windshield scraping, snow shoveling, slipping-on-the-ice (some people call it skating and do it intentionally) season.  But right now, our friends in the Southern Hemisphere are getting ready for heat waves, sunscreen, and (hopefully) air conditioning.  So, in essence, they’re moving towards what we call “Cabinet Cooler Season.”

3. Our Cabinet Cooler Systems are so great, the 316SS Cabinet Cooler Systems with Electronic Temperature Control are actually up for Plant Engineering’s Product of the Year Award.  Because of their 316SS construction, they’re optimally suited for installation in harsh or demanding locations.  The Electronic Temperature Control offers continuous indication of internal temperature, and the ability to change the thermostat setpoint with the push of a button.  If you’re a current user, and you agree that they’re great, we’d appreciate your vote.  If not, I’m reluctant to encourage you to vote for it, but I suppose I can’t stop you from taking my word for it…

EXAIR NEMA 4X 316SS Cabinet Cooler System with Electronic Temperature Control installed on control panel in a pharmaceutical plant.

If you’d like to talk about protecting sensitive electronics from the heat, or from the environment, or both, I’d love to hear from you…give me a call.