Intelligent Compressed Air: Maintaining an Efficient Compressor System

compressor

The electrical costs associated with generating compressed air make it the most expensive utility in any industrial facility. In order to help offset these costs, it’s imperative that the system is operating as efficiently as possible. I’d like to take a moment to walk you through some of the ways that you can work towards making your compressed air system more efficient.

The first step you should take is to identify and fix any leaks within the distribution piping. According to the Compressed Air Challenge, up to 30% of all compressed air generated is lost through leaks. This ends up accounting for nearly 10% of your overall energy costs!! To put leaks in perspective, take a look at the graphic below from the Best Practices for Compressed Air Systems handbook.

air leaks cost

Compressed air leaks don’t just waste energy, but they can also contribute to other operating losses. If enough air is lost through leaks, this can also cause a drop in system pressure. This can affect the functionality of other compressed air operated equipment and processes. This pressure drop can affect the efficiency of the equipment causing it to cycle on/off more frequently or to not work properly. This can lead to anything from rejected products to increased running time. With an increase in running time, there’s also the need for more frequent maintenance and unscheduled downtime.

You can perform a compressed air audit in your facility using an EXAIR Model 9061 Ultrasonic Leak Detector. If you’d prefer someone come in and do this for you, there are several companies that offer energy audit services where this will be a focal point of the process.

ultrasonic_2
EXAIR Ultrasonic Leak Detector

Speaking of maintenance, proper compressor maintenance is also critical to the overall efficiency of the system. Like all industrial equipment, a proper maintenance schedule is required in order to ensure things are operating at peak efficiency. Inadequate compressor maintenance can have a significant impact on energy consumption via lower compressor efficiency. A regular preventative maintenance schedule is required in order to keep things in good shape. The compressor, heat exchanger surfaces, lubricant, lubricant filter, air inlet filter, and dryer all need to be maintained. This can be done yourself or through a reputable compressor dealer. The costs associated with these services are outweighed in the improved reliability and performance of the compressor. A well-maintained system will not cause unexpected shutdowns and will also cost less to operate.

The manner in which you use your compressed air at the point of use should also be evaluated. Inefficient, homemade solutions are thought to be a cheap and quick solution. Unfortunately, the costs to supply these inefficient solutions with compressed air can quickly outweigh the costs of an engineered solution. An engineered compressed air nozzle such as EXAIR’s line of Super Air Nozzles are designed to utilize the coanda effect. Free, ambient air from the environment is entrained into the airflow along with the supplied compressed air. This maximizes the force and flow of the nozzle while keeping compressed air usage to a minimum.

Another method of making your compressed air system more efficient is actually quite simple: regulating the supply pressure. By installing pressure regulators at the point of use for each of your various point of use devices, you can reduce the consumption simply by reducing the pressure. This can’t be done for everything, but I’d be willing to bet that several tasks could be accomplished with the same level of efficiency at a reduced pressure. Most shop air runs at around 80-90 psig, but for general blowoff applications you can often get by operating at a lower pressure. Another simple, but often overlooked, method is to simply shut off the compressed air supply when not in use. If you haven’t yet performed an audit to identify compressed air leaks this is even more of a no-brainer. When operators go to lunch or during breaks, what’s stopping you from just simply turning a valve to shut off the supply of air? It seems simple and minute, but each step goes a long way towards reducing your overall air consumption and ultimately your energy costs.

Tyler Daniel
Application Engineer
E-mail: TylerDaniel@exair.com
Twitter: @EXAIR_TD

 

Image taken from the Best Practices for Compressed Air Systems Handbook, 2nd Edition

Better Understand Your Blowoff Process with EXAIR’s FREE Efficiency Lab

panoramic view
The EXAIR Efficiency Lab

Many customers may not have the means to test the air consumption of their blowoff solutions. With compressed air being the most expensive utility in a manufacturing facility, it’s important to identify places where you can save money on your overall operating costs. EXAIR manufacturers a wide variety of products intended to help you reduce your compressed air usage. If you’re not able to accurately measure the consumption in your own shop, we invite you to send the products into EXAIR for testing. With EXAIR’s Award Winning Efficiency Lab, just simply contact an Application Engineer, box them up and send them to our warehouse in Cincinnati, Ohio.

EXAIR Efficiency Lab

Once we receive it, our engineers will complete some in-depth testing to determine the compressed air consumption, sound level, and force that your current solution provides. With this information, we’ll be able to compare it to an EXAIR Engineered Solution. This way we ensure that you receive the best, safest solution possible also capable of saving money through reduced air consumption and improved efficiency.  We’ll send you back a comprehensive report that’ll help you to make the best decision for your company.

I’ve been recently working with a customer that sent in one of the nozzles they’re using across all their CNC machines. They wanted us to test it out and see if we’re able to offer them something that could reduce their overall compressed air usage. The nozzle was one of the cheap plastic varieties and was attached to a commonly used modular hose. This type of modular hose is not designed for operating under high pressures. These hoses are more suitable for liquid coolant or air that is at or below atmospheric pressure.

IMG_7486
Inefficient and unsafe plastic nozzle

After testing, we found that at 80 psig the nozzle consumed 3.85 SCFM and produced a force of 1.92 oz. We also noticed that after 60 psig, the nozzle began to leak due to a poor seal where the nozzle met the brass hex. The EXAIR nozzle most suitable to replace this was the 1108SS. At just 2.5 SCFM at 80 psig, replacing the plastic nozzle with an engineered solution saves them 35% of their overall consumption for this blowoff. With close to 1000 of these nozzles in operation, that adds up quickly!!

In addition to increasing efficiency, replacing these nozzles also greatly increases overall worker safety. The sound level is reduced from 73 dBA to just 58 dBA and EXAIR’s nozzles also adhere to OSHA 1910.242(b). The plastic nozzles could be dead-ended, posing a hazard that can result in costly fines. These fines are assessed per infraction, so having multiple non-compliant nozzles can easily get very expensive if you’re subject to an unannounced visit by an OSHA inspector.

If you think you may have an opportunity to improve upon your existing blowoff methods, give us a call. We’ll be happy to take a closer look and have you send the product back to EXAIR for a quick trial in our Efficiency Lab. You’ll be glad you did!

Tyler Daniel
Application Engineer
E-mal: TylerDaniel@exair.com
Twitter: @EXAIR_TD

Video Blog: EXAIR Efficiency Lab

The video below is a brief introduction to the EXAIR Efficiency Lab, a free service provided by EXAIR for customers within the USA and Canada.

If you have a single point blowoff that does not have an engineered nozzle, or if you have a wider format blowoff, manifold or home-made drilled pipe, contact an Application Engineer with EXAIR and let us help you to reduce your energy waste. Following are some examples of product where we have helped to save some serious air and reduced noise levels which heightens employee comfort.

Non-engineered blowoffs
Drilled and soldered copper pipe.
Custom manufactured inefficient pipe blowoff

 

The EXAIR Efficiency Lab

Brian Farno
Application Engineer Manager
BrianFarno@EXAIR.com
@EXAIR_BF

ROI – Return on Investment

Return on Investment (ROI) is a measure of the gain (preferably) or loss generated relative to the amount of money that was invested.  ROI is typically expressed as a percentage and is generally used for personal financial decisions, examining the profitability of a company, or comparing different investments.  It can also be used to evaluate a project or process improvement to decide whether spending money on a project makes sense.  The formula is shown below-

ROI

  • A negative ROI says the project would result in an overall loss of money
  • An ROI at zero is neither a loss or gain scenario
  • A positive ROI is a beneficial result, and the larger the value the greater the gain

Gain from investment could include many factors, such as energy savings, reduced scrap savings, cost per part due to increased throughput savings, and many more.  It is important to analyze the full impact and to truly understand all of the savings that can be realized.

Cost of investment also could have many factors, including the capital cost, installation costs, downtime cost for installation, and others.  The same care should be taken to fully capture the cost of the investment.

Example – installing a Super Air Nozzles (14 SCFM compressed air consumption) in place of 1/4″ open pipe (33 SCFM of air consumption consumption) .  Using the Cost Savings Calculator on the EXAIR website, model 1100 nozzle will save $1,710 in energy costs. The model 1100 nozzle costs $37, assuming a $5 compression fitting and $50 in labor to install, the result is a Cost of Investment of $92.00. The ROI calculation for Year 1 is-

ROI2

ROI = 1,759% – a very large and positive value.  Payback time is only 13 working days.

Armed with the knowledge of a high ROI, it should be easier to get projects approved and funded.  Not proceeding with the project costs more than implementing it.

If you have questions regarding ROI and need help in determining the gain and cost from invest values for a project that includes an EXAIR Intelligent Compressed Air® Product, feel free to contact EXAIR and myself or one of our Application Engineers can help you determine the best solution.

Brian Bergmann
Application Engineer

Send me an email
Find us on the Web 
Like us on Facebook
Twitter: @EXAIR_BB